Archive/XCP NUT
Network UPS Tools are a handy set of tools for working with and managing and attached UPS (Uninterruptible Power Supply).
The particular point of this howto is a simple example of how to configure NUT on a pair of Xen XCP dom0 hosts with the following assumptions:
host1 assumed to be attached via USB to the UPS device host2 on the same subnet as master, and is notified over TCP of changes in the power situation host1/host2 are assumed to be powered by the same UPS (e.g. as it was in our office when I wrote this example we had two servers plugged into the UPS) In the below example, host1's IP address is 192.168.41.21 The shutdown example below uses the "xe" command-line tool to shutdown any running XCP guests. I used a Powerware UPS, with the bcmxcp_usb USB driver included with NUT. You will certainly have to make adjustments as needed. This HowTo could definitely be improved by properly utilizing the 'nut' user account to run the management tools (my UPS had issues, so I gave up and ran everything as root), and also the init script could certainly be improved, it was written fairly quickly.
Install NUT on XCP host 1/2
wget http://download.alyseo.com:81/contrib/XenServer/v4.0.96/Nut/nut-2.2-1.i386.rpm rpm -i nut-2.2-1.i386.rpm
Create a basic init script as there doesn't seem to be one in the NUT package I used.
vi /etc/init.d/nut
# Only on HOST2
# Comment out the start/stop lines for upsd and upsdrv, just leave upsmon
# Edit the driver 'bcmxcp_usb' below to match the driver from /usr/local/ups/bin/ that you'll be using.
#
#!/bin/bash
#
# chkconfig: - 80 20
# description: Nut
#
# processname: nut
# config: /usr/local/ups/etc/ups.conf
# pidfile: /var/run/nut
source /etc/rc.d/init.d/functions
RETVAL=0
prog="nut"
upsdrv="/usr/local/ups/bin/upsdrvctl"
drv="bcmxcp_usb"
upsd="/usr/local/ups/sbin/upsd"
ups="upsd"
upsmon="/usr/local/ups/sbin/upsmon"
mon="upsmon"
desc="NUT daemon"
start() {
echo -n $"Starting $desc : "
daemon $upsdrv -u root start
$upsd -u root
$upsmon -u root
RETVAL=$?
echo
[ $RETVAL -eq 0 ] && touch /var/lock/subsys/$prog
return $RETVAL
}
stop() {
echo -n $"Shutting down $desc: "
killproc $drv
killproc $ups
killproc $mon
RETVAL=$?
echo
[ $RETVAL -eq 0 ] && rm -f /var/lock/subsys/$prog
return $RETVAL
}
restart() {
stop
start
}
reload() {
echo -n $"Reloading $desc: "
killproc $drv -HUP
killproc $ups -HUP
killproc $mon -HUP
RETVAL=$?
echo
return $RETVAL
}
case "$1" in
start)
start
;;
stop)
stop
;;
restart)
restart
;;
reload)
reload
;;
condrestart)
[ -e /var/lock/subsys/$prog ] && restart
RETVAL=$?
;;
status)
status $prog
RETVAL=$?
;;
*)
echo $"Usage: $0 {start|stop|restart|reload|condrestart|status}"
RETVAL=1
esac
exit $RETVAL
#
chmod +x /etc/init.d/nut
chkconfig --add nut
Configure NUT on XCP host 1/2
vi /usr/local/ups/etc/ups.conf # comment out everything, add this: user=root [Powerware5110] driver = bcmxcp_usb port = auto vi /usr/local/ups/etc/upsd.conf # comment out everything, add this: #use the below on HOST1 LISTEN localhost 3493 LISTEN 192.168.41.21 3493 ACL all 0.0.0.0/0 ACL localhost 127.0.0.1/32 ACL office 192.168.41.0/24 ACCEPT localhost ACCEPT office REJECT all #use the below on HOST2 ACL all 0.0.0.0/0 ACL localhost 127.0.0.1/32 ACCEPT localhost REJECT all # vi /usr/local/ups/etc/upsd.users # comment out everything, add this: [local_mon] password = MYPASSWORD allowfrom = localhost upsmon master [office_mon] password = MYPASSWORD allowfrom = office upsmon master # vi /usr/local/ups/etc/upsmon.conf # # HOST1 (master with UPS attached) MONITOR Powerware5110@localhost 1 local_mon MYPASSWORD master SHUTDOWNCMD "xe vm-shutdown --multiple power-state=running && /sbin/shutdown -h +0" # HOST2 (slave just networked to master) MONITOR Powerware5110@192.168.41.21 1 office_mon MYPASSWORD master SHUTDOWNCMD "xe vm-shutdown --multiple power-state=running && /sbin/shutdown -h +0" #
Start everything up, run on both host1/host2
#start the service service nut start #run this to get some stats from the UPS to check connectivity /usr/local/ups/bin/upsc Powerware5110